Definitions. As used in this section, the following terms shall have the meanings indicated:
ANSI
American National Standards Institute.
BATTERY
A single cell or a group of cells connected together electrically in series, in parallel, or a combination of both, which can charge, discharge, and store energy electrochemically. For the purposes of this section, batteries utilized in consumer products are excluded from these requirements.
BATTERY ENERGY STORAGE MANAGEMENT SYSTEM
An electronic system that protects storage batteries from operating outside their safe operating parameters and disconnects electrical power to the energy storage system or places it in a safe condition if potentially hazardous temperatures or other conditions are detected. The system generates an alarm and trouble signal for off normal conditions.
BATTERY ENERGY STORAGE SYSTEM
A system consisting of electrochemical storage batteries, battery chargers, controls, power conditioning systems and associated electrical equipment, assembled together, capable of storing energy in order to supply electrical energy at a future time, not to include a stand-alone twelve-volt car battery or an electric motor vehicle. A battery energy storage system is classified as a Tier 1 or Tier 2 battery energy storage system as follows:
(1)
Tier 1 battery energy storage systems have an aggregate energy capacity less than or equal to 80 kWh and, if in a room or enclosed area, consist of only a single energy storage system technology.
(a)
Battery energy storage systems for one- to two-family residential dwellings within or outside the structure with an aggregate energy capacity that shall not exceed:
[1]
Forty kWh within utility closets and storage or utility spaces.
[2]
Eighty kWh in attached or detached garages and detached accessory structures.
[3]
Eighty kWh on exterior walls.
[4]
Eighty kWh outdoors on the ground.
(2)
Tier 2 battery energy storage systems have an aggregate energy capacity greater than 80 kWh or are comprised of more than one storage battery technology in a room or enclosed area.
CELL
The basic electrochemical unit, characterized by an anode and a cathode, used to receive, store, and deliver electrical energy.
COMMISSIONING
A systematic process that provides documented confirmation that a battery energy storage system functions according to the intended design criteria and complies with applicable code requirements.
DEDICATED-USE BUILDING
A building that is built for the primary intention of housing battery energy storage system equipment and is classified as Group F-1 occupancy as defined in the International Building Code. It is constructed in accordance with the Uniform Code, and it complies with the following:
(1)
The building's only permitted primary use is for battery energy storage, energy generation, and other electrical grid-related operations.
(2)
No other occupancy types are permitted in the building.
(3)
Occupants in the rooms and areas containing battery-energy storage systems are limited to personnel that operate, maintain, service, test, and repair the battery energy storage system and other energy systems.
(4)
Administrative and support personnel are permitted in incidental-use areas within the buildings that do not contain battery energy storage system, provided the following:
(a)
The areas do not occupy more than 10% of the building area of the story in which they are located.
(b)
A means of egress is provided from the incidental-use areas to a public way that does not require occupants to traverse through areas containing battery energy storage systems or other energy systems.
DWELLING UNIT
A building or portion thereof or immobile house trailer, which is used, occupied or maintained as living quarters for one family only and providing complete housekeeping facilities; except that for specialized housing as provided for in RSP Districts, living quarters may consist of sleeping accommodations only, plus individual bathrooms, such dwelling unit having one full kitchen only, free access within the dwelling unit on all floors, one main entrance and only one meter each for gas, electricity and water.
ENERGY CODE
The New York State Energy Conservation Construction Code adopted pursuant to Article 11 of the Energy Law, as currently in effect and as hereafter amended from time to time.
FIRE CODE
The fire code section of the New York State Uniform Fire Prevention and Building Code adopted pursuant to Article 18 of the Executive Law, as currently in effect and as hereafter amended from time to time.
NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL)
A U.S. Department of Labor designation recognizing a private sector organization to perform certification for certain products to ensure that they meet the requirements of both the construction and general industry OSHA electrical standards.
NEC
National Electric Code.
NFPA
National Fire Protection Association.
NONDEDICATED-USE BUILDING
All buildings that contain a battery energy storage system and do not comply with the dedicated-use building requirements, including all other occupancy types such as, but not limited to, commercial, industrial, offices, and multifamily housing.
NONPARTICIPATING PROPERTY
Any property that is not a participating property.
NONPARTICIPATING RESIDENCE
Any residence located on nonparticipating property.
OCCUPIED COMMUNITY BUILDING
Any building in Occupancy Group A, B, E, I, R, as defined in the International Building Code, including but not limited to schools, colleges, day-care facilities, hospitals, correctional facilities, public libraries, theaters, stadiums, apartments, hotels, and houses of worship.
PARTICIPATING PROPERTY
A battery energy storage system host property or any real property that is the subject of an agreement that provides for the payment of monetary compensation to the landowner from the battery energy storage system owner (or affiliate) regardless of whether any part of a battery energy storage system is constructed on the property.
SPECIAL FLOOD HAZARD AREA
The land area covered by the floodwaters of the base flood is the special flood hazard area (SFHA) on NFIP maps. The SFHA is the area where the National Flood Insurance Program's (NFIP's) floodplain management regulations must be enforced and the area where the mandatory purchase of flood insurance applies.
UL
Underwriters Laboratory, an accredited standards developer in the United States.
UNIFORM CODE
The New York State Uniform Fire Prevention and Building Code adopted pursuant to Article 18 of the Executive Law, as currently in effect and as hereafter amended from time to time.