84 CONDOMINIUM CONVERSIONS
Unit Type | Minimum Floor Area |
|---|---|
Bachelor/studio/single | 500 square feet |
One-bedroom | 700 square feet |
Two-bedroom | 900 square feet |
Three-bedroom | 1100 square feet |
Each additional bedroom | 150 square feet |
Number of Stories | Building Wall Length | ||||||
|---|---|---|---|---|---|---|---|
20 | 40 | 60 | 80 | 100 | 120 | 140 | |
1 | 7 | 8 | 9 | 10 | 11 | 12 | 13 |
2 | 8 | 9 | 10 | 11 | 12 | 13 | 14 |
Based on the following formula: |
4 feet + 2 feet (for each story) +1 foot for each 20 feet of building wall length |
Unit Type | Minimum Floor Area |
|---|---|
Bachelor and single | 500 square feet |
One bedroom | 700 square feet |
Two-bedroom | 900 square feet |
Three-bedroom | 1,100 square feet |
Each additional bedroom | 150 square feet |
Table 1.0 MINIMUM REQUIRED POINT VALUE TO ADDRESS NONCOMPLIANT DEVELOPMENT STANDARD | ||
|---|---|---|
Development Standards Available for Deviation | Limitations | Points Required to Allow Deviation |
Minimum lot size | The total deviation shall be a maximum of 10% reduction of the otherwise minimum required lot size. | 50 |
Height of building or structure | The total deviation shall not increase the applicable building or structure height by more than 10% of the otherwise maximum height, nor does the deviation allow the existing structures to exceed the maximum allowable habitable story. | 25 |
Setbacks | The total deviation shall not reduce the applicable setbacks by more than 10% of those otherwise required. | 25 (per setback) |
Building separation | A minimum separation between buildings shall be no less than 10 feet. | 25 |
Building bulk | 50 | |
Open space | The total modification shall not decrease the required open space more than 20% of the otherwise required open space more than twenty percent (20%) of the otherwise required usable open space. | 50 |
Accessory building standards | ||
Setback | 25 | |
Size | 25 | |
Height | 25 | |
Garage that abuts alley | 25 | |
Building separation | 25 | |
Variation in wall setback | 25 | |
Table 2.0 DESIRABLE SITE DESIGN AND ARCHITECTURAL ELEMENTS | |||
|---|---|---|---|
Desirable Elements | Definition of Element | Maximum Points that Can be Accrued | |
1. | Recreation room | Provide a recreation room with recreational equipment located in a common area accessible for all residents to utilize. | 25 |
2. | Playground area | Provide a playground area and playground equipment located in a common area accessible for all residents to utilize. | 25 |
3. | Gym | Provide a gym complete with gym equipment located accessible for all residents to utilize. | 25 |
4. | Swimming pool | Provide a swimming pool located in a common area accessible for all residents to utilize. | 25 |
5. | Daycare | Provide daycare facilities located in a common area accessible for all residents to utilize; priority shall be given to residents of complex. | 25 |
6. | Barbeque picnic area | Provide a barbeque/picnic area complete with tables and chairs located in a common area accessible for all residents to utilize. | 25 |
7. | Exceed on-site parking | For every one parking space provided by the developer which exceeds the City's parking requirements. | 50 |
8. | Open space over the minimum requirement | Developer must provide at least 5% over the minimum required open space. | 25 |
9. | Decorative hardscape for driveways | Developer must use paving material other than plain asphalt or concrete. Interlocking unit pavers are preferred, but stamped, colored concrete is acceptable. A minimum of at least 20% of the total surface area of the driveway including each driveway entrance must be comprised of decorative hardscape material in order to be eligible for this category. | 15 |
10. | Upgraded roof materials | The use of quality dimensional roof materials. The roof material must be rated for a minimum of 40 years. | 15 |
11. | Mix of building materials (other than stucco) | Introduce and incorporate different exterior wall materials over at least 20% of the building wall surface other than stucco, including stone and/or brick veneer; wood siding; etc. Materials should be consistently applied and should be chosen to work harmoniously with adjacent materials and the architectural style of the building. Piecemeal embellishment does not qualify. | 25 |
12. | Eliminate large blank exterior walls | Provide varied architectural treatments and articulation. Incorporate features such as varied building elevation plane depth, bay windows, corbels, cornice treatments and other similar architectural details. The intent is to provide visually-interesting design that has compatible architectural treatments. | 25 |
13. | Functional/open front porch | Front porches must have a minimum of five feet by eight feet. | 25 |
14. | Provide appearance of front porch or entryway | Architectural articulation on the front of the residential structure which resembles a porch throughout the project. | 10 |
15. | Provide strong entry | Architectural articulation on the front of the unit which provides a "sense of entry." | 10 |
16. | Provide double front doors or single door with side-lights | Use of double front doors or a single front door with decorative side-lights throughout the project. | 10 |
17. | Provide larger trees, shrubs and vegetation along front elevation to soften views of the front elevation. | Provide larger trees (larger than 48 inch box), 10 gallon shrubs, and other proportionately sized plant materials throughout the project. | 10 |
18. | Provide less building height than permitted in the City zoning ordinance | Points will be given if the residence is built at a height less than the building height requirements mandated by the City Zoning Ordinance. | 25 |
19. | Increase the amount of front, rear, and side yard setback | Points will be given if front, rear, and side yard setbacks exceed the requirements mandated by the City Zoning Ordinance by at least 10%. | 25 (per setback) |
20. | Provide varying roof planes and ridgelines | Provide varying roof planes and ridgelines to eliminate identical roof ridgelines. | 25 |
21. | Provide varying roof massing | Design must minimize large expanses of the roof to ensure the roof does not dominate the overall view of the building elevation. The use of dormers, additional gables, and similar design features can be considered. | 25 |
22. | Alley loaded garages | All homes must have access from a rear alley. | 50 |
23. | Garage not facing the street | Garage doors must be located to the rear of the residence and beyond the major plane of the building that faces the street. | 50 |
24. | Licensed professional | All plans and conceptual elevations to be prepared by appropriate licensed professional (i.e., American Institute of Architects (A.I.A)). | 25 |
25. | Different building elevation appearance | Each residential unit within the project site has a different building elevation design. | 25 |
C. | Attenuation of Noise. | ||
1. | General. Wall and floor-ceiling assemblies separating units from each other or from public or quasi-public spaces such as interior corridors, laundry rooms, recreation rooms, and garages shall provide airborne sound insulation for walls, and both airborne and impact sound insulation for floor-ceiling assemblies. | ||
2. | Airborne Sound Insulation. All wall assemblies described in the previous paragraph shall be of a type of construction that has a minimum rating of 50 STC (Sound Transmission Class). All floor/ceiling assemblies described or alluded to in the previous paragraph shall be of a type of construction that has a minimum rating of 50 STC. Wood floor joists and subflooring shall not be continuous between separate units. Penetrations or openings in the construction for piping, electrical outlets and devices, recess cabinets, bathtubs, soffits, heating and ventilating and/or air conditioning intake and exhaust ducts, and the like, shall be sealed, lined, insulated or otherwise treated to maintain the required rating and such treatment shall be approved by the Building Official. Entrance doors to the unit shall be of solid construction and, together with perimeter seals, shall have a minimum rating of 26 STC. Such perimeter seals shall be maintained in effective operating condition. | ||
3. | Impact Sound Insulation. All separating floor/ceiling assemblies described in the previous paragraphs shall be of a type of construction that has a minimum rating of 50 IIC (Impact Insulation Class). Floor coverings may be included in the assembly to obtain the required ratings, but must be retained as a permanent part of the assembly. | ||
4. | Verification of Sound and Impact Class. STC and IIC ratings shall be based on the results of laboratory measurements and will not be subjected to field testing. The STC rating shall be based on the American Society for Testing and Materials System specified in ATSM E 90 and E 413 or equivalent. The IIC rating shall be based on the system in use at the National Bureau of Standards or equivalent. Ratings obtained from other testing procedures will require adjustment to the above rating systems. In documenting wall and floor/ceiling compliance with the required sound ratings, the applicant shall furnish the City either: | ||
a. | Data based on tests performed by a recognized testing laboratory; or; | ||
b. | Verified manufacturers data on the ratings of the various wall and floor/ceiling assemblies utilized in the project. | ||
5. | Other Requirements. In addition to the above requirements, all requirements as set forth in California Administrative Code, Title 25, Sections 1092 and 1094 or their successors shall be met. | ||
D. | Fire Prevention and Maintenance. Smoke detectors shall be provided conforming to current Building Code requirements in each individual dwelling unit. Fire hydrants, fire alarms, fire extinguishers, sprinkler systems and other appliances or apparatus shall be retained in good operable conditions at all times. | ||
E. | Underground Utility Services. Prior to occupancy of any units in a project, the applicant shall provide the Building Department with two sets of as-built drawings for all underground utility services and sewer lines. One set will be held by the Building Department until the HOA becomes functional, at which time, they shall be given to the HOA. | ||
F. | Report of the Building Official. The Building Official or designee shall make an inspection of the proposed condominium conversion project to determine compliance with life safety standards and any other codes/standards of the currently adopted Construction Codes. This inspection shall be at the expense of the owner/developer. The inspection by the Building Official is in conjunction with the Physical and Structural Elements Reports and is a means and resource in gaining and verifying code compliance for the proposed project. Prior to Planning Commission consideration of a condominium project involving existing buildings, the Building Official or designee shall submit a report to the Director of Community Development specifying where the building(s) are deficient with respect to life safety standards or any other pertinent standards in the currently adopted Construction Codes. | ||
G. | The developer shall provide each perspective buyer with a statement listing a history of conversion repairs and a copy of the inspection reports. | ||
H. | The developer shall post moneys for the HOA to be used for large scale repairs. Such money shall be held in a bona fide trust account, to be held separately from accounts for regular monthly maintenance fees. The use of maintenance fees shall be established by the City-approved by-laws for each development, with the intent being for major repairs affecting the entire complex. | ||
84 CONDOMINIUM CONVERSIONS
Unit Type | Minimum Floor Area |
|---|---|
Bachelor/studio/single | 500 square feet |
One-bedroom | 700 square feet |
Two-bedroom | 900 square feet |
Three-bedroom | 1100 square feet |
Each additional bedroom | 150 square feet |
Number of Stories | Building Wall Length | ||||||
|---|---|---|---|---|---|---|---|
20 | 40 | 60 | 80 | 100 | 120 | 140 | |
1 | 7 | 8 | 9 | 10 | 11 | 12 | 13 |
2 | 8 | 9 | 10 | 11 | 12 | 13 | 14 |
Based on the following formula: |
4 feet + 2 feet (for each story) +1 foot for each 20 feet of building wall length |
Unit Type | Minimum Floor Area |
|---|---|
Bachelor and single | 500 square feet |
One bedroom | 700 square feet |
Two-bedroom | 900 square feet |
Three-bedroom | 1,100 square feet |
Each additional bedroom | 150 square feet |
Table 1.0 MINIMUM REQUIRED POINT VALUE TO ADDRESS NONCOMPLIANT DEVELOPMENT STANDARD | ||
|---|---|---|
Development Standards Available for Deviation | Limitations | Points Required to Allow Deviation |
Minimum lot size | The total deviation shall be a maximum of 10% reduction of the otherwise minimum required lot size. | 50 |
Height of building or structure | The total deviation shall not increase the applicable building or structure height by more than 10% of the otherwise maximum height, nor does the deviation allow the existing structures to exceed the maximum allowable habitable story. | 25 |
Setbacks | The total deviation shall not reduce the applicable setbacks by more than 10% of those otherwise required. | 25 (per setback) |
Building separation | A minimum separation between buildings shall be no less than 10 feet. | 25 |
Building bulk | 50 | |
Open space | The total modification shall not decrease the required open space more than 20% of the otherwise required open space more than twenty percent (20%) of the otherwise required usable open space. | 50 |
Accessory building standards | ||
Setback | 25 | |
Size | 25 | |
Height | 25 | |
Garage that abuts alley | 25 | |
Building separation | 25 | |
Variation in wall setback | 25 | |
Table 2.0 DESIRABLE SITE DESIGN AND ARCHITECTURAL ELEMENTS | |||
|---|---|---|---|
Desirable Elements | Definition of Element | Maximum Points that Can be Accrued | |
1. | Recreation room | Provide a recreation room with recreational equipment located in a common area accessible for all residents to utilize. | 25 |
2. | Playground area | Provide a playground area and playground equipment located in a common area accessible for all residents to utilize. | 25 |
3. | Gym | Provide a gym complete with gym equipment located accessible for all residents to utilize. | 25 |
4. | Swimming pool | Provide a swimming pool located in a common area accessible for all residents to utilize. | 25 |
5. | Daycare | Provide daycare facilities located in a common area accessible for all residents to utilize; priority shall be given to residents of complex. | 25 |
6. | Barbeque picnic area | Provide a barbeque/picnic area complete with tables and chairs located in a common area accessible for all residents to utilize. | 25 |
7. | Exceed on-site parking | For every one parking space provided by the developer which exceeds the City's parking requirements. | 50 |
8. | Open space over the minimum requirement | Developer must provide at least 5% over the minimum required open space. | 25 |
9. | Decorative hardscape for driveways | Developer must use paving material other than plain asphalt or concrete. Interlocking unit pavers are preferred, but stamped, colored concrete is acceptable. A minimum of at least 20% of the total surface area of the driveway including each driveway entrance must be comprised of decorative hardscape material in order to be eligible for this category. | 15 |
10. | Upgraded roof materials | The use of quality dimensional roof materials. The roof material must be rated for a minimum of 40 years. | 15 |
11. | Mix of building materials (other than stucco) | Introduce and incorporate different exterior wall materials over at least 20% of the building wall surface other than stucco, including stone and/or brick veneer; wood siding; etc. Materials should be consistently applied and should be chosen to work harmoniously with adjacent materials and the architectural style of the building. Piecemeal embellishment does not qualify. | 25 |
12. | Eliminate large blank exterior walls | Provide varied architectural treatments and articulation. Incorporate features such as varied building elevation plane depth, bay windows, corbels, cornice treatments and other similar architectural details. The intent is to provide visually-interesting design that has compatible architectural treatments. | 25 |
13. | Functional/open front porch | Front porches must have a minimum of five feet by eight feet. | 25 |
14. | Provide appearance of front porch or entryway | Architectural articulation on the front of the residential structure which resembles a porch throughout the project. | 10 |
15. | Provide strong entry | Architectural articulation on the front of the unit which provides a "sense of entry." | 10 |
16. | Provide double front doors or single door with side-lights | Use of double front doors or a single front door with decorative side-lights throughout the project. | 10 |
17. | Provide larger trees, shrubs and vegetation along front elevation to soften views of the front elevation. | Provide larger trees (larger than 48 inch box), 10 gallon shrubs, and other proportionately sized plant materials throughout the project. | 10 |
18. | Provide less building height than permitted in the City zoning ordinance | Points will be given if the residence is built at a height less than the building height requirements mandated by the City Zoning Ordinance. | 25 |
19. | Increase the amount of front, rear, and side yard setback | Points will be given if front, rear, and side yard setbacks exceed the requirements mandated by the City Zoning Ordinance by at least 10%. | 25 (per setback) |
20. | Provide varying roof planes and ridgelines | Provide varying roof planes and ridgelines to eliminate identical roof ridgelines. | 25 |
21. | Provide varying roof massing | Design must minimize large expanses of the roof to ensure the roof does not dominate the overall view of the building elevation. The use of dormers, additional gables, and similar design features can be considered. | 25 |
22. | Alley loaded garages | All homes must have access from a rear alley. | 50 |
23. | Garage not facing the street | Garage doors must be located to the rear of the residence and beyond the major plane of the building that faces the street. | 50 |
24. | Licensed professional | All plans and conceptual elevations to be prepared by appropriate licensed professional (i.e., American Institute of Architects (A.I.A)). | 25 |
25. | Different building elevation appearance | Each residential unit within the project site has a different building elevation design. | 25 |
C. | Attenuation of Noise. | ||
1. | General. Wall and floor-ceiling assemblies separating units from each other or from public or quasi-public spaces such as interior corridors, laundry rooms, recreation rooms, and garages shall provide airborne sound insulation for walls, and both airborne and impact sound insulation for floor-ceiling assemblies. | ||
2. | Airborne Sound Insulation. All wall assemblies described in the previous paragraph shall be of a type of construction that has a minimum rating of 50 STC (Sound Transmission Class). All floor/ceiling assemblies described or alluded to in the previous paragraph shall be of a type of construction that has a minimum rating of 50 STC. Wood floor joists and subflooring shall not be continuous between separate units. Penetrations or openings in the construction for piping, electrical outlets and devices, recess cabinets, bathtubs, soffits, heating and ventilating and/or air conditioning intake and exhaust ducts, and the like, shall be sealed, lined, insulated or otherwise treated to maintain the required rating and such treatment shall be approved by the Building Official. Entrance doors to the unit shall be of solid construction and, together with perimeter seals, shall have a minimum rating of 26 STC. Such perimeter seals shall be maintained in effective operating condition. | ||
3. | Impact Sound Insulation. All separating floor/ceiling assemblies described in the previous paragraphs shall be of a type of construction that has a minimum rating of 50 IIC (Impact Insulation Class). Floor coverings may be included in the assembly to obtain the required ratings, but must be retained as a permanent part of the assembly. | ||
4. | Verification of Sound and Impact Class. STC and IIC ratings shall be based on the results of laboratory measurements and will not be subjected to field testing. The STC rating shall be based on the American Society for Testing and Materials System specified in ATSM E 90 and E 413 or equivalent. The IIC rating shall be based on the system in use at the National Bureau of Standards or equivalent. Ratings obtained from other testing procedures will require adjustment to the above rating systems. In documenting wall and floor/ceiling compliance with the required sound ratings, the applicant shall furnish the City either: | ||
a. | Data based on tests performed by a recognized testing laboratory; or; | ||
b. | Verified manufacturers data on the ratings of the various wall and floor/ceiling assemblies utilized in the project. | ||
5. | Other Requirements. In addition to the above requirements, all requirements as set forth in California Administrative Code, Title 25, Sections 1092 and 1094 or their successors shall be met. | ||
D. | Fire Prevention and Maintenance. Smoke detectors shall be provided conforming to current Building Code requirements in each individual dwelling unit. Fire hydrants, fire alarms, fire extinguishers, sprinkler systems and other appliances or apparatus shall be retained in good operable conditions at all times. | ||
E. | Underground Utility Services. Prior to occupancy of any units in a project, the applicant shall provide the Building Department with two sets of as-built drawings for all underground utility services and sewer lines. One set will be held by the Building Department until the HOA becomes functional, at which time, they shall be given to the HOA. | ||
F. | Report of the Building Official. The Building Official or designee shall make an inspection of the proposed condominium conversion project to determine compliance with life safety standards and any other codes/standards of the currently adopted Construction Codes. This inspection shall be at the expense of the owner/developer. The inspection by the Building Official is in conjunction with the Physical and Structural Elements Reports and is a means and resource in gaining and verifying code compliance for the proposed project. Prior to Planning Commission consideration of a condominium project involving existing buildings, the Building Official or designee shall submit a report to the Director of Community Development specifying where the building(s) are deficient with respect to life safety standards or any other pertinent standards in the currently adopted Construction Codes. | ||
G. | The developer shall provide each perspective buyer with a statement listing a history of conversion repairs and a copy of the inspection reports. | ||
H. | The developer shall post moneys for the HOA to be used for large scale repairs. Such money shall be held in a bona fide trust account, to be held separately from accounts for regular monthly maintenance fees. The use of maintenance fees shall be established by the City-approved by-laws for each development, with the intent being for major repairs affecting the entire complex. | ||