OPERATING STANDARDS
This article contains performance and operating standards applicable within the city. These uses must be approved for the site on which they will take place by the appropriate procedures prescribed in Article XI. Once the use is approved for the site, the following procedures and standards must be complied with before commencement of the use and thereafter during its operation.
The following standards shall apply to all uses on incorporated lands in the City of Carrabelle approved under this code.
A.
The following devices and instruments standardized by the American Standards Association shall be used:
S.L.M. Sound Level Meter
V.M.D. Three Component Vibration Measuring Device
A.D.I. Atmospheric Dust Impinger
B.
One of the following devices or its equivalent for measuring cup flash points shall be used:
Pensky-Martens
Tagliabue
C.
The following references are cited in this section:
NOTE: Wherever the standards for industrial safety or air contamination cited herein have been superseded or preempted by other regulatory agencies, the more stringent standards shall apply.
Unless otherwise defined herein, all terminology shall be in conformance with applicable publication of the American National Standards Institute, Incorporated (ANSI) or its successor body.
Instrumentation used in making sound level measurements shall meet the following requirements:
A.
Sound level meter. Sound level meters shall be of at least Type 2 meeting ANSI 51.4-1971 requirements. Alternately, a microphone or sound level meter may be used with a magnetic tape recorder and/or graphic level recorder or indicating meter, providing the system meets at least Type 2 ANSI requirements. For measurements requiring octave band analysis, the equipment will additionally meet ANSI 51-11-1966.
B.
Sound level calibrator. The entire sound measurement system shall be calibrated with an acoustic calibrator recommended by the manufacturer and according to the manufacturer's recommended procedures.
C.
Windscreen. An open-call, foam windscreen recommended by the manufacturer of the sound level meter shall be used.
D.
Calibration. The instruments used for acoustical measurements shall be serviced in accordance with the manufacturer's instructions. Before and after a series of measurements, the instrumentation shall be calibrated acoustically according to the manufacturer's instructions and at intervals not exceeding two hours when the instrument is used no longer than a two-hour period.
E.
Meter operation. Unless expressed otherwise in this section, the sound level meter shall be operated in accordance with instrument manufacturer's instruction and as follows:
1.
Microphone location. The microphone shall be located at a height of four feet above the ground level. All microphone positions shall be described in the recording of all data.
2.
Microphone orientation. The microphone shall be oriented in relation to the source of the sound in accordance with instrument manufacturer's instructions. Where the instruction manual is vague or does not include adequate information, a specific recommendation shall be obtained from the manufacturer.
3.
Meter setting. The meter shall be set for the A-weighted network and fast response.
4.
Ambient sound. Measurements shall be made only when the A-weighted ambient sound level, including wind effects and all sources other than that being measured, is at least ten dB lower than the sound level of the source.
F.
Persons selected to conduct sound measurement tests shall have received training in the techniques of sound measurement and the operation of sound measurement instruments.
G.
The technician making direct readings of the meter shall be positioned in relation to the microphone in accordance with the instrument manufacturer's instructions. Where the instruction manual is vague or does not include adequate information, a specific recommendation shall be obtained from the manufacturer.
The following procedure shall be used to determine if a violation exists pursuant to the requirements of this section:
A.
The sound level meter shall be located on the adjacent boundary closest to the noise source or on a lot from which complaint arises, unless specified otherwise.
B.
If a complaint arises from a multi-story structure, the height of the sound level meter shall be adjusted so that it is on a direct line between the noise source and noise receiver.
C.
The microphone shall be at least three feet from any adjacent structure.
D.
Following equipment manufacturer's operation instruction, determine if the sound pressure level in the one-third octave band with the tone exceeds the arithmetic average of the sound pressure level of the two contiguous bands by:
5 dB for center frequencies of 500 Hz and above.
8 dB for center frequencies between 160—400 Hz.
15 dB for center frequencies of 125 Hz or below.
E.
Record readings as follows:
1.
Every ten seconds read the level of the sound level meter.
2.
Record this level on a data sheet at the appropriate level.
3.
After 60 samples, test by the confidence criterion described below. If the samples meet the criterion, then the measurement is complete. If not, then 40 more samples must be taken and the confidence criterion is still not met, additional groups of 50 samples must be completed until the confidence criterion is met.
F.
Test confidence criterion as follows:
1.
Counting down from the top of the data sheet circle the "test samples". After the first 60 samples have been taken, then the 2nd, 6th, and 12th samples from the top are circled.
2.
If those three test samples fall into three continuous levels, then the measurement is complete. Otherwise, another group of samples must be taken and tested again.
3.
If 100 or more samples have been taken, skewing is allowed, The 2 outer test samples (the error limits) can be shifted by one sample (not one level) both in the same direction. This sometimes provides the necessary accuracy without requiring further sampling. However, if the criterion is still not met after skewing, the 50 more samples must be taken and tested.
4.
Once the confidence criterion has been met, the level exceeding ten percent of the measurement period (the second sample circle) has been determined with dB with 95 percent confidence.
G.
As noise source radiates sound, read the maximum deflection of the needle of the sound level meter. If possible, determine and record the minimum sound level during the period of observations.
H.
The following procedure shall be used to determine if a violation exists pursuant to requirements for multi-family dwellings:
1.
The microphone of the sound level meter shall be set at any point 4 feet from wall, ceiling or floor that is radiating noise and at least 3 feet from any adjacent structure.
2.
Determine if sound is pure tone.
3.
Use appropriate measurement procedure described above.
4.
If possible, repeat procedure for different microphone locations.
I.
Officials trained in the enforcement of the Florida Motor Vehicle Noise Prevention and Control Act of 1974, Chapter 74-110, Laws of Florida, shall follow the procedure described in Department of Environmental Regulations Rules, Florida Administrative Code, Chapters 17-18, Vehicle Sound Measurement, Part I, Highway Vehicle Test Procedure to determine motor vehicle sound levels.
J.
The following shall be obtained and reported for each sound measurement period:
1.
Dimensioned sketch or photograph of the test area showing location of sound source(s) and receivers.
2.
Note any possible reflecting objects within test area.
3.
Physical and topographical description of the ground surface.
4.
Meteorological conditions, including temperature, relative humidity, wind direction and speed.
5.
Equipment and settings used for sound measurement.
6.
Date, time and length of measurement period.
7.
Measured sound level(s).
8.
Background sound level.
No person shall unnecessarily make or continue to make any noise disturbance as set forth below.
1.
Creating or causing the creation of any sound within or adjacent to any noise sensitive zone, containing a hospital, nursing home, school, or other designated areas, so as to interfere with the functions of such activity or annoy the occupants of the facility, provided that conspicuous signs are displayed indicating the presence of the zone to read: "Quiet Zone."
2.
Operating or permitting the operation within a multi-family dwelling any source of sound, in such a manner as to exceed 55 dBA from 7:00 a.m. to 10:00 p.m. or 45 dBA from 10:00 p.m. to 7:0 a.m. when measured within an adjacent intra-building dwelling. These noise limits shall not be exceeded more than 10 percent of any measurement period, which shall not be less than ten minutes.
3.
Operating or permitting to be operated, any loudspeaker or other source of sound in any public place that exceeds the levels shown in the table below at any point normally occupied by a customer, without a conspicuous and legible sign stating "WARNING. SOUND LEVELS WITHIN MAY CAUSE PERMANENT HEARING IMPAIRMENT."
PERMISSIBLE NOISE EXPOSURE
4.
Using or firing explosives, firearms, or similar devices such that the sound therefrom creates a noise disturbance so as to violate the provisions of this section, or within a noise sensitive zone, public space or public right-of-way is prohibited. Licensed game-hunting activities on property where such activities are authorized shall not be so regulated.
A.
Maximum sustained sound. No person shall operate or cause to be operated any source of sound in such a manner as to create a sound level which exceeds the limits set forth for the receiving land use category in the table below, more than ten percent of any measurement period, which shall not be less than ten minutes when measured at the property boundary of the receiving land use.
SOUND LEVELS BY RECEIVING LAND USE
B.
Maximum intermittent sound. For any source of sound received at the property boundary of the receiving land use, the maximum sound level shall not exceed the sound level limits in the table above by:
1.
Ten dBA from 7:00 a.m. to 10:00 p.m.
2.
Five dBA from 10:00 p.m. to 7:00 a.m.
3.
Ten dBA at all times in a manufacturing, industrial or agricultural land use.
A.
It shall not be the intent of this section to regulate noises in circumstances where persons, property, wildlife or plant life are not affected by the noise. The following activities or sources are exempt, except during certain hours as specified below:
1.
Activities covered by the following: stationary, nonemergency signaling devices, emergency signaling devices, domestic power tools, air-conditioning and air-handling equipment for residential purposes, operating motor vehicles, refuse collection vehicles;
2.
The unamplified human voice;
3.
Railway locomotives and cars;
4.
The lowing of cattle, the clucking of fowl, the neighing of horses, the baying of hounds, or other normal sounds of reasonably cared for agricultural or domestic animals, as well as the sounds of necessary farming equipment for a bona fide agricultural operation;
5.
Aircraft operations;
6.
Construction or routine maintenance of public service utilities;
7.
Houses of worship bells or chimes (see B.5 below); or
8.
Activities regulated by the Franklin County Mining regulations.
B.
The following are exempted, except during the hours or time limits specified:
1.
Radios, television sets, musical instruments and similar devices. Operating, playing of any radio, television, phonograph, drum, musical instrument, or similar device which produces or reproduces sound:
a.
Between the hours of 10:00 p.m. and 7:00 a.m. the following day in such a manner as to create a noise disturbance into a residentially developed area so as to violate the provisions of this section.
b.
In such a manner as to exceed the levels set forth for public space in this section, measured at a distance of at least 50 feet from such device operating on a public right-of-way or public space.
2.
Loudspeakers. Using or operating for any purpose any loudspeaker, loudspeaker system, or similar device between the hours of 10:00 p.m. and 7:00 a.m. the following day, such that the sound therefrom creates a noise disturbance into a residentially committed and developed area so as to violate the provisions of this section. This section shall not apply to public school activities and special public assembly events approved by the governing body.
3.
Loading and unloading. Loading, unloading, closing or other handling of boxes, crates, containers, building materials, or similar objects between the hours of 10:00 p.m. and 6:00 a.m. the following day in such a manner as to cause a noise disturbance into a residential area or so as to at anytime violate the provisions of this section.
4.
Construction. Operating or causing the operation of any tools or equipment used in construction, drilling, repair, blasting, alteration, or demolition work between the hours of 7:00 p.m. and 7:00 a.m. the following day, such that the sound therefrom creates a noise disturbance into a residentially committed and developed area so as to violate the provisions of this section, except for emergency work of public service utilities. This section shall not apply to the use of domestic power tools as specified in this section.
5.
Stationary nonemergency signaling devices. Sounding or permitting the sounding of any electronically amplified signal from any stationary bell, chime, siren, whistle, or similar device, intended primarily for nonemergency purposes, from any place, for more than ten seconds in any hourly period shall be prohibited. Houses of worship shall not be governed by this provision.
6.
The intentional sounding or permitting the sounding outdoors of any fire, burglar, or civil defense alarm, siren, whistle, or similar stationary emergency purposes or for testing. Testing of a stationary emergency signaling device shall not occur between the hours of 7:00 p.m. and 7:00 a.m. the following day. Any such testing shall only use the minimum cycle test time. In no case shall such test exceed 60 seconds. Testing of the complete emergency signaling system, including the functioning of the signaling device and the personnel response to the signaling device, shall not occur more than once in each calendar month. Such testing shall not occur between the hours of 10:00 p.m. and 7:00 a.m. the following day.
7.
Sounding or permitting the sounding of any exterior burglar or fire alarm or any motor vehicle burglar alarm unless, such alarm is automatically terminated within 15 minutes of activation, shall be prohibited.
8.
Operating or permitting the operating of any mechanically powered saw, sander, drill, grinder, lawn or garden tool, or similar tool between 10:00 p.m. and 7:00 a.m. the following day so as to create a noise disturbance into a residentially developed area in violation of the provisions of this section, shall be prohibited. Any motor, machinery, pumps, etc., shall be properly muffled not to create a noise disturbance, as defined by the provisions of this section.
9.
Refuse collection vehicles. No person shall collect refuse with a refuse collection vehicle between the hours of 7:00 p.m. and 6:00 a.m. the following day in a residentially committed and developed area or noise sensitive zone. The provisions of this section shall not apply to the emission of sound for the purpose of alerting persons to the existence of an emergency, or the emission of sound in the performance of emergency work.
Except where a person is acting in good faith to comply with an abatement order, violation of any provision of this code shall be cause for a notice of violation to be issued by the chief of police.
Where an industry or commercial business has established its use away from other incompatible uses and subsequently, through the encroachment of development, now finds itself adjoining a receiving land category which would require a reduction in noise generation, said industry or commercial business shall not be required to retrofit any mechanical device solely for the purpose of complying with noise abatement.
A.
For the purpose of measuring vibration, a three-component simultaneous measuring system recognized as standard for such purpose shall be used in determining displacement and maximum peak particle velocity. Maximum peak particle velocity shall be the maximum displacement vector sums of the three perpetual components referred to above multiplied by the frequency in cycles per second. Location and timing of measurements shall be arranged insofar as possible to exclude vibrations emanating from off the premises involved, or a correction factor reasonable under the circumstances shall be applied to compensate for off-premises vibrations.
B.
In industrial districts, impact vibrations from any use, at any point beyond district boundaries, shall not exceed the levels set out in paragraph D below.
C.
In all other districts, impact vibrations from any use shall not exceed, at any point beyond the property lines of the use, the levels set forth in paragraph D below.
D.
Maximum permitted impact vibration peak particle velocity (in inches per second) shall be as follows:
1.
0.1 peak particle velocity at one or less Hz in any plane.
2.
0.37 at 4 - 12 Hz.
3.
1.0 at 30 Hz or above.
E.
The provisions of this section shall not apply to activities regulated by Franklin County mining regulations.
To protect and enhance the air quality of Carrabelle and environs, all sources of air pollution shall comply with rules set forth by the Environmental Protection Agency in Code of Federal Regulations, Title 40 and the Florida Department of Environmental Regulations in Florida Administrative Code, Chapter 17-2. No person shall operate a regulated source of air pollution without a valid operation permit issued by the Florida Department of Environmental Regulation.
Air pollution emissions shall be tested and results reported in accordance with techniques and methods adopted by the Florida Department of Environmental Regulation and submitted to the State. These tests shall be carried out under the supervision of the State and at the expense of the person responsible for the source of pollution.
A.
In any district, no odor shall be permitted at any lot line exceeding the lowest amount set forth in Table III, Odor Thresholds", of Chapter 5, "Physiological Effects", of the APAM. For compounds not described in Table III, odor thresholds may be established by methods indicated in Chapter 5 of the manual, and no odor shall be permitted at any lot line exceeding the amount determined by the application of such methods.
B.
In all districts, the concentration of toxic or noxious matter shall not exceed, at any point at or beyond any lot line, one-tenth of the maximum allowable concentration set forth in Section 12-20 of ICR12 measured with the A.D.I.
In all districts in which the storage, use, or manufacture of flammable or explosive materials is permitted, the following regulations shall apply:
A.
Storage and utilization of solid materials or products which are incombustible, or which in themselves support combustion and are consumed slowly as they burn, is permitted.
B.
Storage, utilization, or manufacture of solid materials or products including free burning and intense burning is permitted provided that said materials or products shall be stored, utilized, or manufactured within completely enclosed buildings having noncombustible walls and protected throughout by an automatic fire extinguishing system. The requirements for an automatic fire extinguishing system may be waived by the fire chief in those cases where the introduction of water to a burning substance would cause additional hazard.
C.
Outdoor storage of coal and other solid fuels is permitted provided storage is in conformance with the "Fire Protection Handbook" 1986 Edition, printed by the National Fire Protection Association.
D.
Storage, utilization or manufacture of flammable and combustible liquids, or materials which produce flammable or explosive vapors or gases shall be permitted in accordance with NFPA Fire Code #30, exclusive of storage of finished products in original sealed containers.
Table 9.02.07.01 CLASSIFICATION OF LIQUIDS
In all districts, no use, activity, or process shall be conducted which produces electric and/or magnetic fields which adversely affect public health, safety, and welfare including but not limited to interference with normal radio/telephone/or television reception from off the premises where the activity is conducted.
OPERATING STANDARDS
This article contains performance and operating standards applicable within the city. These uses must be approved for the site on which they will take place by the appropriate procedures prescribed in Article XI. Once the use is approved for the site, the following procedures and standards must be complied with before commencement of the use and thereafter during its operation.
The following standards shall apply to all uses on incorporated lands in the City of Carrabelle approved under this code.
A.
The following devices and instruments standardized by the American Standards Association shall be used:
S.L.M. Sound Level Meter
V.M.D. Three Component Vibration Measuring Device
A.D.I. Atmospheric Dust Impinger
B.
One of the following devices or its equivalent for measuring cup flash points shall be used:
Pensky-Martens
Tagliabue
C.
The following references are cited in this section:
NOTE: Wherever the standards for industrial safety or air contamination cited herein have been superseded or preempted by other regulatory agencies, the more stringent standards shall apply.
Unless otherwise defined herein, all terminology shall be in conformance with applicable publication of the American National Standards Institute, Incorporated (ANSI) or its successor body.
Instrumentation used in making sound level measurements shall meet the following requirements:
A.
Sound level meter. Sound level meters shall be of at least Type 2 meeting ANSI 51.4-1971 requirements. Alternately, a microphone or sound level meter may be used with a magnetic tape recorder and/or graphic level recorder or indicating meter, providing the system meets at least Type 2 ANSI requirements. For measurements requiring octave band analysis, the equipment will additionally meet ANSI 51-11-1966.
B.
Sound level calibrator. The entire sound measurement system shall be calibrated with an acoustic calibrator recommended by the manufacturer and according to the manufacturer's recommended procedures.
C.
Windscreen. An open-call, foam windscreen recommended by the manufacturer of the sound level meter shall be used.
D.
Calibration. The instruments used for acoustical measurements shall be serviced in accordance with the manufacturer's instructions. Before and after a series of measurements, the instrumentation shall be calibrated acoustically according to the manufacturer's instructions and at intervals not exceeding two hours when the instrument is used no longer than a two-hour period.
E.
Meter operation. Unless expressed otherwise in this section, the sound level meter shall be operated in accordance with instrument manufacturer's instruction and as follows:
1.
Microphone location. The microphone shall be located at a height of four feet above the ground level. All microphone positions shall be described in the recording of all data.
2.
Microphone orientation. The microphone shall be oriented in relation to the source of the sound in accordance with instrument manufacturer's instructions. Where the instruction manual is vague or does not include adequate information, a specific recommendation shall be obtained from the manufacturer.
3.
Meter setting. The meter shall be set for the A-weighted network and fast response.
4.
Ambient sound. Measurements shall be made only when the A-weighted ambient sound level, including wind effects and all sources other than that being measured, is at least ten dB lower than the sound level of the source.
F.
Persons selected to conduct sound measurement tests shall have received training in the techniques of sound measurement and the operation of sound measurement instruments.
G.
The technician making direct readings of the meter shall be positioned in relation to the microphone in accordance with the instrument manufacturer's instructions. Where the instruction manual is vague or does not include adequate information, a specific recommendation shall be obtained from the manufacturer.
The following procedure shall be used to determine if a violation exists pursuant to the requirements of this section:
A.
The sound level meter shall be located on the adjacent boundary closest to the noise source or on a lot from which complaint arises, unless specified otherwise.
B.
If a complaint arises from a multi-story structure, the height of the sound level meter shall be adjusted so that it is on a direct line between the noise source and noise receiver.
C.
The microphone shall be at least three feet from any adjacent structure.
D.
Following equipment manufacturer's operation instruction, determine if the sound pressure level in the one-third octave band with the tone exceeds the arithmetic average of the sound pressure level of the two contiguous bands by:
5 dB for center frequencies of 500 Hz and above.
8 dB for center frequencies between 160—400 Hz.
15 dB for center frequencies of 125 Hz or below.
E.
Record readings as follows:
1.
Every ten seconds read the level of the sound level meter.
2.
Record this level on a data sheet at the appropriate level.
3.
After 60 samples, test by the confidence criterion described below. If the samples meet the criterion, then the measurement is complete. If not, then 40 more samples must be taken and the confidence criterion is still not met, additional groups of 50 samples must be completed until the confidence criterion is met.
F.
Test confidence criterion as follows:
1.
Counting down from the top of the data sheet circle the "test samples". After the first 60 samples have been taken, then the 2nd, 6th, and 12th samples from the top are circled.
2.
If those three test samples fall into three continuous levels, then the measurement is complete. Otherwise, another group of samples must be taken and tested again.
3.
If 100 or more samples have been taken, skewing is allowed, The 2 outer test samples (the error limits) can be shifted by one sample (not one level) both in the same direction. This sometimes provides the necessary accuracy without requiring further sampling. However, if the criterion is still not met after skewing, the 50 more samples must be taken and tested.
4.
Once the confidence criterion has been met, the level exceeding ten percent of the measurement period (the second sample circle) has been determined with dB with 95 percent confidence.
G.
As noise source radiates sound, read the maximum deflection of the needle of the sound level meter. If possible, determine and record the minimum sound level during the period of observations.
H.
The following procedure shall be used to determine if a violation exists pursuant to requirements for multi-family dwellings:
1.
The microphone of the sound level meter shall be set at any point 4 feet from wall, ceiling or floor that is radiating noise and at least 3 feet from any adjacent structure.
2.
Determine if sound is pure tone.
3.
Use appropriate measurement procedure described above.
4.
If possible, repeat procedure for different microphone locations.
I.
Officials trained in the enforcement of the Florida Motor Vehicle Noise Prevention and Control Act of 1974, Chapter 74-110, Laws of Florida, shall follow the procedure described in Department of Environmental Regulations Rules, Florida Administrative Code, Chapters 17-18, Vehicle Sound Measurement, Part I, Highway Vehicle Test Procedure to determine motor vehicle sound levels.
J.
The following shall be obtained and reported for each sound measurement period:
1.
Dimensioned sketch or photograph of the test area showing location of sound source(s) and receivers.
2.
Note any possible reflecting objects within test area.
3.
Physical and topographical description of the ground surface.
4.
Meteorological conditions, including temperature, relative humidity, wind direction and speed.
5.
Equipment and settings used for sound measurement.
6.
Date, time and length of measurement period.
7.
Measured sound level(s).
8.
Background sound level.
No person shall unnecessarily make or continue to make any noise disturbance as set forth below.
1.
Creating or causing the creation of any sound within or adjacent to any noise sensitive zone, containing a hospital, nursing home, school, or other designated areas, so as to interfere with the functions of such activity or annoy the occupants of the facility, provided that conspicuous signs are displayed indicating the presence of the zone to read: "Quiet Zone."
2.
Operating or permitting the operation within a multi-family dwelling any source of sound, in such a manner as to exceed 55 dBA from 7:00 a.m. to 10:00 p.m. or 45 dBA from 10:00 p.m. to 7:0 a.m. when measured within an adjacent intra-building dwelling. These noise limits shall not be exceeded more than 10 percent of any measurement period, which shall not be less than ten minutes.
3.
Operating or permitting to be operated, any loudspeaker or other source of sound in any public place that exceeds the levels shown in the table below at any point normally occupied by a customer, without a conspicuous and legible sign stating "WARNING. SOUND LEVELS WITHIN MAY CAUSE PERMANENT HEARING IMPAIRMENT."
PERMISSIBLE NOISE EXPOSURE
4.
Using or firing explosives, firearms, or similar devices such that the sound therefrom creates a noise disturbance so as to violate the provisions of this section, or within a noise sensitive zone, public space or public right-of-way is prohibited. Licensed game-hunting activities on property where such activities are authorized shall not be so regulated.
A.
Maximum sustained sound. No person shall operate or cause to be operated any source of sound in such a manner as to create a sound level which exceeds the limits set forth for the receiving land use category in the table below, more than ten percent of any measurement period, which shall not be less than ten minutes when measured at the property boundary of the receiving land use.
SOUND LEVELS BY RECEIVING LAND USE
B.
Maximum intermittent sound. For any source of sound received at the property boundary of the receiving land use, the maximum sound level shall not exceed the sound level limits in the table above by:
1.
Ten dBA from 7:00 a.m. to 10:00 p.m.
2.
Five dBA from 10:00 p.m. to 7:00 a.m.
3.
Ten dBA at all times in a manufacturing, industrial or agricultural land use.
A.
It shall not be the intent of this section to regulate noises in circumstances where persons, property, wildlife or plant life are not affected by the noise. The following activities or sources are exempt, except during certain hours as specified below:
1.
Activities covered by the following: stationary, nonemergency signaling devices, emergency signaling devices, domestic power tools, air-conditioning and air-handling equipment for residential purposes, operating motor vehicles, refuse collection vehicles;
2.
The unamplified human voice;
3.
Railway locomotives and cars;
4.
The lowing of cattle, the clucking of fowl, the neighing of horses, the baying of hounds, or other normal sounds of reasonably cared for agricultural or domestic animals, as well as the sounds of necessary farming equipment for a bona fide agricultural operation;
5.
Aircraft operations;
6.
Construction or routine maintenance of public service utilities;
7.
Houses of worship bells or chimes (see B.5 below); or
8.
Activities regulated by the Franklin County Mining regulations.
B.
The following are exempted, except during the hours or time limits specified:
1.
Radios, television sets, musical instruments and similar devices. Operating, playing of any radio, television, phonograph, drum, musical instrument, or similar device which produces or reproduces sound:
a.
Between the hours of 10:00 p.m. and 7:00 a.m. the following day in such a manner as to create a noise disturbance into a residentially developed area so as to violate the provisions of this section.
b.
In such a manner as to exceed the levels set forth for public space in this section, measured at a distance of at least 50 feet from such device operating on a public right-of-way or public space.
2.
Loudspeakers. Using or operating for any purpose any loudspeaker, loudspeaker system, or similar device between the hours of 10:00 p.m. and 7:00 a.m. the following day, such that the sound therefrom creates a noise disturbance into a residentially committed and developed area so as to violate the provisions of this section. This section shall not apply to public school activities and special public assembly events approved by the governing body.
3.
Loading and unloading. Loading, unloading, closing or other handling of boxes, crates, containers, building materials, or similar objects between the hours of 10:00 p.m. and 6:00 a.m. the following day in such a manner as to cause a noise disturbance into a residential area or so as to at anytime violate the provisions of this section.
4.
Construction. Operating or causing the operation of any tools or equipment used in construction, drilling, repair, blasting, alteration, or demolition work between the hours of 7:00 p.m. and 7:00 a.m. the following day, such that the sound therefrom creates a noise disturbance into a residentially committed and developed area so as to violate the provisions of this section, except for emergency work of public service utilities. This section shall not apply to the use of domestic power tools as specified in this section.
5.
Stationary nonemergency signaling devices. Sounding or permitting the sounding of any electronically amplified signal from any stationary bell, chime, siren, whistle, or similar device, intended primarily for nonemergency purposes, from any place, for more than ten seconds in any hourly period shall be prohibited. Houses of worship shall not be governed by this provision.
6.
The intentional sounding or permitting the sounding outdoors of any fire, burglar, or civil defense alarm, siren, whistle, or similar stationary emergency purposes or for testing. Testing of a stationary emergency signaling device shall not occur between the hours of 7:00 p.m. and 7:00 a.m. the following day. Any such testing shall only use the minimum cycle test time. In no case shall such test exceed 60 seconds. Testing of the complete emergency signaling system, including the functioning of the signaling device and the personnel response to the signaling device, shall not occur more than once in each calendar month. Such testing shall not occur between the hours of 10:00 p.m. and 7:00 a.m. the following day.
7.
Sounding or permitting the sounding of any exterior burglar or fire alarm or any motor vehicle burglar alarm unless, such alarm is automatically terminated within 15 minutes of activation, shall be prohibited.
8.
Operating or permitting the operating of any mechanically powered saw, sander, drill, grinder, lawn or garden tool, or similar tool between 10:00 p.m. and 7:00 a.m. the following day so as to create a noise disturbance into a residentially developed area in violation of the provisions of this section, shall be prohibited. Any motor, machinery, pumps, etc., shall be properly muffled not to create a noise disturbance, as defined by the provisions of this section.
9.
Refuse collection vehicles. No person shall collect refuse with a refuse collection vehicle between the hours of 7:00 p.m. and 6:00 a.m. the following day in a residentially committed and developed area or noise sensitive zone. The provisions of this section shall not apply to the emission of sound for the purpose of alerting persons to the existence of an emergency, or the emission of sound in the performance of emergency work.
Except where a person is acting in good faith to comply with an abatement order, violation of any provision of this code shall be cause for a notice of violation to be issued by the chief of police.
Where an industry or commercial business has established its use away from other incompatible uses and subsequently, through the encroachment of development, now finds itself adjoining a receiving land category which would require a reduction in noise generation, said industry or commercial business shall not be required to retrofit any mechanical device solely for the purpose of complying with noise abatement.
A.
For the purpose of measuring vibration, a three-component simultaneous measuring system recognized as standard for such purpose shall be used in determining displacement and maximum peak particle velocity. Maximum peak particle velocity shall be the maximum displacement vector sums of the three perpetual components referred to above multiplied by the frequency in cycles per second. Location and timing of measurements shall be arranged insofar as possible to exclude vibrations emanating from off the premises involved, or a correction factor reasonable under the circumstances shall be applied to compensate for off-premises vibrations.
B.
In industrial districts, impact vibrations from any use, at any point beyond district boundaries, shall not exceed the levels set out in paragraph D below.
C.
In all other districts, impact vibrations from any use shall not exceed, at any point beyond the property lines of the use, the levels set forth in paragraph D below.
D.
Maximum permitted impact vibration peak particle velocity (in inches per second) shall be as follows:
1.
0.1 peak particle velocity at one or less Hz in any plane.
2.
0.37 at 4 - 12 Hz.
3.
1.0 at 30 Hz or above.
E.
The provisions of this section shall not apply to activities regulated by Franklin County mining regulations.
To protect and enhance the air quality of Carrabelle and environs, all sources of air pollution shall comply with rules set forth by the Environmental Protection Agency in Code of Federal Regulations, Title 40 and the Florida Department of Environmental Regulations in Florida Administrative Code, Chapter 17-2. No person shall operate a regulated source of air pollution without a valid operation permit issued by the Florida Department of Environmental Regulation.
Air pollution emissions shall be tested and results reported in accordance with techniques and methods adopted by the Florida Department of Environmental Regulation and submitted to the State. These tests shall be carried out under the supervision of the State and at the expense of the person responsible for the source of pollution.
A.
In any district, no odor shall be permitted at any lot line exceeding the lowest amount set forth in Table III, Odor Thresholds", of Chapter 5, "Physiological Effects", of the APAM. For compounds not described in Table III, odor thresholds may be established by methods indicated in Chapter 5 of the manual, and no odor shall be permitted at any lot line exceeding the amount determined by the application of such methods.
B.
In all districts, the concentration of toxic or noxious matter shall not exceed, at any point at or beyond any lot line, one-tenth of the maximum allowable concentration set forth in Section 12-20 of ICR12 measured with the A.D.I.
In all districts in which the storage, use, or manufacture of flammable or explosive materials is permitted, the following regulations shall apply:
A.
Storage and utilization of solid materials or products which are incombustible, or which in themselves support combustion and are consumed slowly as they burn, is permitted.
B.
Storage, utilization, or manufacture of solid materials or products including free burning and intense burning is permitted provided that said materials or products shall be stored, utilized, or manufactured within completely enclosed buildings having noncombustible walls and protected throughout by an automatic fire extinguishing system. The requirements for an automatic fire extinguishing system may be waived by the fire chief in those cases where the introduction of water to a burning substance would cause additional hazard.
C.
Outdoor storage of coal and other solid fuels is permitted provided storage is in conformance with the "Fire Protection Handbook" 1986 Edition, printed by the National Fire Protection Association.
D.
Storage, utilization or manufacture of flammable and combustible liquids, or materials which produce flammable or explosive vapors or gases shall be permitted in accordance with NFPA Fire Code #30, exclusive of storage of finished products in original sealed containers.
Table 9.02.07.01 CLASSIFICATION OF LIQUIDS
In all districts, no use, activity, or process shall be conducted which produces electric and/or magnetic fields which adversely affect public health, safety, and welfare including but not limited to interference with normal radio/telephone/or television reception from off the premises where the activity is conducted.