A. In the data center industrial district, no building or premises shall be used and no building shall hereafter be erected, converted in use, enlarged, moved or structurally altered unless otherwise provided in this title, except for one or more of the following uses:
Agriculture.
Data Center.
Any use permitted in any commercial district.
Any use permitted in the restricted industrial district.
Uses customarily incidental to the foregoing uses and accessory buildings and structures
B. The following uses are strictly prohibited whether or not they are located in a fully enclosed building:
Ammunition manufacture, storage or warehousing.
Automobile wrecking yard.
Explosives manufacture, storage or warehousing.
Fireworks manufacture, storage or warehousing.
Inflammable gases or liquids manufacture, storage or warehousing (except in conjunction with the operation of an airport).
Junkyard.
(Ord. 2026-01, 1-5-2026)
10-23-2: HEIGHT, YARDS, AREA AND OTHER REQUIREMENTS:
In the data center industrial district, the height of buildings, minimum dimensions of yards, minimum lot area, vision clearance, off street parking and other requirements shall be as follows for all buildings hereafter erected, converted in used, enlarged, moved or structurally altered:
A. Height: Forty five feet (45') or three (3) stories, whichever is least.
B. Front Yard Setback: There shall be a front yard setback of four hundred feet (400').
C. Side Yard Setback: There shall be a front yard setback of four hundred feet (400').
D. Rear Yard Setback: There shall be a front yard setback of four hundred feet (400').
E. Lot Area: Same as provided in section 14-4-7 of this code.
F. Vision Clearance: Same as provided in subsection 10-4-5G of this title.
G. Off Street Parking: Same as provided in section 10-4-7 of this title. (Ord. 2026-01, 1-5-2026)