All installations shall be properly connected with the Keansburg Municipal Utilities Authority water system, prior to the issuance of a certificate of occupancy.
Minimum fire flows shall be based on recommendations by the American Insurance Association and the National Board of Fire Underwriters, as indicated in Exhibits 4 and 5[1].
Hydrants shall be spaced to provide necessary fire flow, and the average area per hydrant typically should not exceed 120,000 square feet. In addition, hydrants shall be spaced so that each residence shall be within 500 feet of a hydrant.
Hydrants shall be located at the end of lines, and valves of full line size shall be provided after hydrants tees at the ends of all dead lines and lines which may be extended in the future.
All installations shall be properly connected with the Keansburg Municipal Utilities Authority water system, prior to the issuance of a certificate of occupancy.
Minimum fire flows shall be based on recommendations by the American Insurance Association and the National Board of Fire Underwriters, as indicated in Exhibits 4 and 5[1].
Hydrants shall be spaced to provide necessary fire flow, and the average area per hydrant typically should not exceed 120,000 square feet. In addition, hydrants shall be spaced so that each residence shall be within 500 feet of a hydrant.
Hydrants shall be located at the end of lines, and valves of full line size shall be provided after hydrants tees at the ends of all dead lines and lines which may be extended in the future.