search icon

West Orange City Zoning Code

§ 25-14.3

Minimum Levels of Illumination.

[Ord. No. 2357-12 § 25-14.2; amended 9-22-2020 by Ord. No. 2617-20]
Minimum Levels of Illumination
Pedestrian Walkways
Parking Areas
Streets
RG
4/0.4
5/0.5
4/0.4
RM
4/0.4
5/0.5
4/0.4
Cluster
4/0.4
5/0.5
4/0.4
PURD
4/0.4
5/0.5
4/0.4
OB-1
6/0.6
16/1.5
6/0.6
OB-2
6/0.6
16/1.5
6/0.6
B-1
10/0.9
20/2.0
13/1.2
B-2
10/0.9
20/2.0
13/1.2
PC
10/0.9
16/1.5
13/1.2
OR
4/0.4
11/1.0
6/0.06
I
4/0.4
11/1.0
6/0.06
Parking garage*
75/7.5
54
Circulation aisles
110/10
*Day conditions are listed; night conditions
54/5
Lux/Footcandles
The levels shown are measured in lux/footcandles. The minimum standards are based on the level of light that will be available for new lamps and clean luminaries. When by test or other means it has been determined that less than 80% of the light specified in the minimum standards is attained or a significant number of burnouts are evident, the owner shall be notified and he will have 30 days in which to correct the lighting level to the minimum standards.